• Packaged Solution
• Designed for Recirculation
• Typical System Control +/-2°F
• “Out of Temperature Range” Mode
• Remote Set Point Adjustment
• BAS Interface Capability
• New Advanced BAS Features
• Promotes compliance with OSHA, CDC and NYDOH Legionella Guidelines
Water Temperature Control - Recirculation Systems - Electronic features The Brain®. The Brain® is a series of eight Electronic Mixing Centers (EMC) designed specifically for use as the primary water temperature controller in a pumped recirculating hot water system
The complete range has been designed to offer an unparalleled level of system temperature control through the use of precision-engineered hydraulics with integrated electronic circuit technology.
The Brain® Electronic Mixing Centers are available in two flow capacities. To select, simply match the required flow rate on the chart below with a pressure drop acceptable to the system design. Armstrong uses the Modified Hunter Curve, where applicable, when determining system flow requirements.
| The Brain Electronic Mixing Centers | ||||||||||||
| Model | Pressure Drip (psi) | Min. System Draw-Off* | Max.** Flow | Cv | ||||||||
| 5 |
10 |
15 |
20 |
|||||||||
| EMC 1 | 36 | 51 | 62 | 72 | 0 | 58 | 16 | |||||
| EMC 2 | 72 | 102 | 124 | 144 | 0 | 100 | 32 | |||||