Did you know: Ionic beds have years of field-proven success in thousands of electronic humidifier applications.

• Thermal Shutdown Mode
• +/- 2°F Temperature Stability to fixture
• Accuracy at Low Flow Rates
• Maximum Temperature Locking Feature
• Single “sealed for life” Replacement Cartridge
Thermostatic Mixing Valves
Thermostatic
Water Temperature Control - Groups of Fixtures - Thermostatic features a series of individual Thermostatic Mixing Valves designed specifically for use in non-return “dead leg” applications.
The complete range has been designed to offer accurate temperature control in installations where there are diverse flow requirements.
Sizing
When sizing for zoned or group control applications, ensure that there is sufficient residual pressure (20 psi minimum is suggested) after the mixing valve to satisfactorily operate the outlet fixtures at realistic maximum simultaneous demand.
| Rada Thermostatic Mixing Valves (gpm) |
| Model |
Pressure Drip (psi) |
Min. Flow |
Cv |
| 5 |
10 |
15 |
20 |
25 |
30 |
35 |
40 |
45 |
50 |
| 320 |
8 |
11 |
13 |
15 |
17 |
19 |
20 |
22 |
23 |
24 |
1 |
3.4 |
| 425 |
15 |
22 |
27 |
31 |
35 |
38 |
41 |
44 |
46 |
49 |
2 |
6.9 |
| 40 |
36 |
51 |
62 |
72 |
- |
- |
- |
- |
- |
- |
2 |
16.0 |
| 50 |
49 |
70 |
85 |
98 |
- |
- |
- |
- |
- |
- |
2 |
22.0 |
| Rada Thermostatic Mixing Valves (gpm) |
| Model |
Pressure Drip (psi) |
Min. Flow |
Cv |
5
|
10
|
15
|
20
|
| 40/40 |
72 |
101 |
124 |
143 |
16 |
3.4 |
| 50/50 |
98 |
139 |
170 |
197 |
26 |
6.9 |
| 50/50/50 |
148 |
209 |
256 |
295 |
58 |
16.0 |
For an application drawing on Thermostatic Mixing Valves, please click here.