Did you know: You get a live voice when you call Armstrong International, Inc.
Flo-Rite-Temp Model 665PP-PTW-DMC1
Flo-Rite-Temp Model 665PP-PTW-DMC1 Instantaneous Steam/Water Heater pre-piped parallel/redundant tempered water packaged assembly designed for Recirculating Hot Water Systems.
Flo-Rite-Temp Model 665 Pre-Piped (P-P) Parallel (P) Tempered Water (TW) Digital Mixing Center (DMC1) Systems are fully assembled and include the following installation components:
- Steam Trap
- Air Vent
- Thermometers
- CIP Connection Port
- Flow Control/Isolation Valves
- DRV80 Digital Recirculating Valve "The Brain" (DMC1)
Ideal for both new construction and retrofit installation within an existing building infrastructure. Flo-Rite-Temp 665PP-PTW-DMC1 is designed to fit through a standard 32" doorway.
Each Flo-Rite-Temp Model 665PP-PTW-DMC1 Instantaneous Steam/Water Heater features a 6" diameter shell.
Each Flo-Rite-Temp Model 665PP-PTW-DMC1 has 65/130 GPM capacity with 15PSI steam at a 100°F temperature rise.
Each Flo-Rite-Temp Model 535PP-PTW-DMC1 features a unique feed forward design which features a differential pressure diaphragm actuated mixing unit integral to a shell and tube heat exchanger.
The Flo-Rite-Temp Model 665PP-PTW-DMC1 mixing unit manages the water flow through the heat exchanger based upon downstream hot water demand and eliminates the requirement for a modulating steam control valve.
Operating on constant low pressure (2-15PSI) steam, the Flo-Rite-Temp Model 665PP-PTW-DMC1 mixing unit supplies water to the heat exchanger where it is overheated and then returned to the mixing unit for proportional re-mixing with cold water to a pre-set outlet temperature.
The Brain Model DMC1 integrates with the Flo-Rite-Temp Model 665PP-PTW Water Heater to offer a two temperature system option, +/-2°F water temperature control and BAS/LAN connectivity.
To learn more, go to the menu above.
| For submittal drawing refer to: |
| Model 415PP-PTW-EMC1 |
Single Wall |
S5480 |
| Model 415DWPP-PTW-EMC1 |
Double Wall |
S5526 |
| Model 535PP-PTW-DMC1 |
Single Wall |
S5481 |
| Model 535DWPP-PTW-DMC1 |
Double Wall |
S5527 |
| Model 665PP-PTW-DMC1 |
Single Wall |
S5482 |
| Model 665DWPP-PTW-DMC1 |
Double Wall |
S5528 |
| Model 8120PP-PTW-DMC1 |
Single Wall |
S5483 |
| Model 8120DWPP-PTW-DMC1 |
Double Wall |
S5529 |
| Flo-Rite-Temp Instantaneous Steam/Water Heater |
| Model |
Entering Water Temperature |
Outlet Temperature |
| 120 |
130 |
140 |
160 |
180 |
| 415PP-PTW-EMC1 |
40 |
20 |
18 |
16 |
12 |
7 |
| 50 |
20 |
20 |
17 |
13 |
7 |
| 60 |
- |
20 |
19 |
14 |
7 |
| 535PP-PTW-DMC1 |
40 |
45 |
39 |
34 |
26 |
16 |
| 50 |
45 |
43 |
37 |
28 |
17 |
| 60 |
- |
45 |
40 |
30 |
18 |
| 665PP-PTW-DMC1 |
40 |
80 |
73 |
63 |
48 |
32 |
| 50 |
80 |
80 |
68 |
51 |
33 |
| 60 |
- |
80 |
75 |
55 |
35 |
| 8120PP-PTW-DMC1 |
40 |
145 |
145 |
120 |
95 |
59 |
| 50 |
145 |
145 |
134 |
102 |
72 |
| 60 |
- |
145 |
145 |
115 |
90 |
Note: All flow rates in gallons per minute and using 15 PSIG steam.
Note: If a 8120PP-PTW-DMC1 is selected for parallel operation, a second DRV 80 is recommended to increase the flow rate.
Armstrong wants to be your solutions provider: