Did you know: Armstrong’s complete range of products can be found on the Federal Government’s GSA schedule.

Recirculating Hot Water Systems

Recirculating Hot Water Systems

 

Recirculating Hot Water Systems

Double Wall Pre-Piped Tempered Water (DWP-PTW)

Flo-Rite-Temp Instantaneous Steam/Water Heater for Recirculating Hot Water Systems feature four double wall heat exchanger options offered as pre-piped tempered water packaged assemblies.

Flo-Rite-Temp Double Wall (DW) Pre-Piped (P-P) Tempered Water (TW) Systems are fully assembled and include the following installation components:

  • Steam Trap
  • Air Vent
  • Thermometers
  • CIP Connection Port
  • Flow Control/Isolation Valves
  • DRV 80 Digital Recirculating Valve "The Brain" (DMC1)

Ideal for both new construction and retrofit installation within an existing building infrastructure. Flo-Rite-Temp Double Wall Pre-Piped Tempered Water (DWP-PTW) Systems are designed to fit through a standard 32" doorway (Model 8120 36" doorway).

The DW (double wall) version of the Flo-Rite-Temp instantaneous water heater uses a double-wall tube to provide positive separation of the steam and water in the heat exchanger. The area between the walls of the tubes vents to atmosphere so you can detect tube failure without cross-contaminating either the steam or water. The Flo-Rite-Temp DW is well suited for all hot water applications where steam is available and plumbing codes or safety requirements prevent the heating medium and the potable water supply from being cross-contaminated.

Armstrong Flo-Rite-Temp Instantaneous Steam/Water Heater pre-piped packages are available in 58 standard configurations.

Customized Hot Water System Solutions are our specialty. Multiple orientations, configurations and options are available.

Hot Water System Solutions which include condensate recovery, circulating pumps, additional mixed water temperature controls/loops and varied other components can be application engineered specifically to meet the projects requirements.

To learn more, go to the menu above.

 For submittal drawing refer to:
 Model 415P-PTW-EMC1   Single Wall   S5476
 Model 415DWP-PTW-EMC1   Double Wall   S5522
 Model 535P-PTW-DMC1   Single Wall   S5477
 Model 535DWP-PTW-DMC1   Double Wall   S5523
 Model 665P-PTW-DMC1   Single Wall   S5478
 Model 665DWP-PTW-DMC1   Double Wall   S5524
 Model 8120P-PTW-DMC1   Single Wall   S5479
 Model 8120DWP-PTW-DMC1   Double Wall   S5525

 

 Flo-Rite-Temp Instantaneous Steam/Water Heater
Model Entering Water Temperature Outlet Temperature
120 130 140 160 180
415DWP-PTW-EMC1 40 20 18 16 12 7
50 20 20 17 13 7
60 - 20 19 14 7
535DWP-PTW-DMC1 40 45 39 34 26 16
50 45 43 37 28 17
60 - 45 40 30 18
665DWP-PTW-DMC1 40 80 73 63 48 32
50 80 80 68 51 33
60 - 80 75 55 35
8120DWP-PTW-DMC1 40 145 145 120 95 59
50 145 145 134 102 72
60 - 145 145 115 90

   Note: All flow rates in gallons per minute and using 15 PSIG steam.