Did you know: Armstrong has an inline tool to repair faulty radiator valves without turning off the steam or water.

Flo-Rite-Temp Model 8120P-P

Flo-Rite-Temp Model 8120P-P

Flo-Rite-Temp Model 8120 P-P Instantaneous Steam/Water Heater pre-piped single temperature packaged assembly designed for a Non-Recirculating Hot Water System.

Flo-Rite-Temp Model 8120 Pre-Piped (P-P) Single Temperature Systems are fully assembled and include the following installation components:

  • Steam Trap
  • Air Vent
  • Thermometers
  • CIP Connection Port
  • Flow Control/Isolation Valves

Ideal for both new construction and retrofit installation within an existing building infrastructure. Flo-Rite-Temp 8120P-P is designed to fit through a standard 36" doorway.

Flo-Rite-Temp Model 8120P-P Instantaneous Steam/Water Heater features a 8" diameter shell and a non-helical straight internal tube bundle with end cap.

Flo-Rite-Temp Model 8120P-P has 120 GPM capacity with 15PSI steam at a 100°F temperature rise.

Flo-Rite-Temp Model 8120P-P features a unique feed forward design which features a differential pressure diaphragm actuated mixing unit integral to a shell and tube heat exchanger.

The Flo-Rite-Temp Model 8120P-P mixing unit manages the water flow through the heat exchanger based upon downstream hot water demand and eliminates the requirement for a modulating steam control valve.

Operating on constant low pressure (2-15PSI) steam, the Flo-Rite-Temp Model 8120P-P mixing unit supplies water to the heat exchanger where it is overheated and then returned to the mixing unit for proportional re-mixing with cold water to a pre-set outlet temperature.

To learn more, go to the menu above.

 

 For submittal drawing refer to:
 Model 415P-P   Single Wall   S5453
 Model 415DWP-P   Double Wall   S5499
 Model 535P-P   Single Wall   S5454
 Model 535DWP-P  Double Wall   S5500
 Model 665P-P   Single Wall   S5455
 Model 665DWP-P   Double Wall   S5501
 Model 8120P-P   Single Wall   S5456
 Model 8120DWP-P   Double Wall   S5502

 

 Flo-Rite-Temp Instantaneous Steam/Water Heater
Model Entering Water Temperature Outlet Temperature
120 130 140 160 180
415P-P 40 20 18 16 12 7
50 20 20 17 13 7
60 - 20 19 14 7
535P-P 40 45 39 34 26 16
50 45 43 37 28 17
60 - 45 40 30 18
665P-P 40 80 73 63 48 32
50 80 80 68 51 33
60 - 80 75 55 35
8120P-P 40 145 145 120 95 59
50 145 145 134 102 72
60 - 145 145 115 90

   Note: All flow rates in gallons per minute and using 15 PSIG steam.

 

 


Armstrong wants to be your solutions provider: