Flo-Rite-Temp Model 415DWP-P

Flo-Rite-Temp Model 415DWP-P

Flo-Rite-Temp Model 415DWP-P

Flo-Rite-Temp Model 415DWP-P Instantaneous Steam/Water Heater pre-piped single temperature packaged assembly designed for a Non-Recirculating Hot Water System.

Flo-Rite-Temp Model 415DWP-P double wall instantaneous water heater uses a double-wall tube to provide positive separation of the steam and water in the heat exchanger. The area between the walls of the tubes vents to atmosphere so you can detect tube failure without cross-contaminating either the steam or water. The Flo-Rite-Temp 415DWP-P is well suited for all hot water applications where steam is available and plumbing codes or safety requirements prevent the heating medium and the potable water supply from being cross-contaminated.

Flo-Rite-Temp Model 415 Double Wall (DW) Pre-Piped (P-P) Single Temperature Systems are fully assembled and include the following installation components:

  • Steam Trap
  • Air Vent
  • Thermometers
  • CIP Connection Port
  • Flow Control/Isolation Valves

Ideal for both new construction and retrofit installation within an existing building infrastructure. Flo-Rite-Temp Model 415DWP-P is designed to fit through a standard 32" doorway.

Flo-Rite-Temp Model 415DWP-P Instantaneous Steam/Water Heater features a 4" diameter shell and a non-helical straight internal tube bundle with end cap.

Flo-Rite-Temp Model 415DWP-P has 15 GPM capacity with 15PSI steam at a 100°F temperature rise.

Flo-Rite-Temp Model 415DWP-P features a unique feed forward design which features a differential pressure diaphragm actuated mixing unit integral to a shell and tube heat exchanger.

The Flo-Rite-Temp Model 415DWP-P mixing unit manages the water flow through the heat exchanger based upon downstream hot water demand and eliminates the requirement for a modulating steam control valve.

Operating on constant low pressure (2-15PSI) steam, the Flo-Rite-Temp Model 415DWP-P mixing unit supplies water to the heat exchanger where it is overheated and then returned to the mixing unit for proportional re-mixing with cold water to a pre-set outlet temperature.

 
 For submittal drawing refer to:
 Model 415P-P   Single Wall   S5453
 Model 415DWP-P   Double Wall   S5499
 Model 535P-P   Single Wall   S5454
 Model 535DWP-P   Double Wall   S5500
 Model 665P-P   Single Wall   S5455
 Model 665DWP-P   Double Wall   S5501
 Model 8120P-P   Single Wall   S5456
 Model 8120DWP-P   Double Wall   S5502

 Flo-Rite-Temp Instantaneous Steam/Water Heater
Model Entering Water Temperature Outlet Temperature
120 130 140 160 180
415DWP-P 40 20 18 16 12 7
50 20 20 17 13 7
60 - 20 19 14 7
535DWP-P 40 45 39 34 26 16
50 45 43 37 28 17
60 - 45 40 30 18
665DWP-P 40 80 73 63 48 32
50 80 80 68 51 33
60 - 80 75 55 35
8120DWP-P 40 145 145 120 95 59
50 145 145 134 102 72
60 - 145 145 115 90

   Note: All flow rates in gallons per minute and using 15 PSIG steam.





Resource Library
Resource Library
Contact Us
Contact Us
Find a Rep
Find a Rep
Request a Quote
Request a Quote
System Assessment
System Assessment
Calculators
Calculators
View Cart
View Cart