For pressures to 900 psig (62 bar) . . .
Capacities to 11,000 lb/hr (4990 kg/hr)
SH Series Superheat Steam Traps operate by the effect that rising temperature has on the thermostatic bimetallic elements.
At start-up, the valve is wide open, which allows a large volume of non-condensables and cold condensate to be removed from the system. When the system reaches steam temperature, the elements become sufficiently hot to pull on the trap’s valve stem, closing the valve.
The valve remains closed until the bimetallic elements cool, thus allowing the valve to crack open, vent the condensate and non-condensables, and then close again when steam temperature is reached.
The SH Series Superheat Steam Traps adjust automatically to changing conditions. Hot elements in the valve generate forces to offset rises in pressure.
Carbon Steel
For pressures to 250 psig (17 bar) . . .
Capacities to 5,000 lb/hr (2267 kg/hr)
Stainless Steel
For pressures to 900 psig (62 bar) . . .
Capacities to 11,000 lb/hr (4990 kg/hr)
For help in specifying the exact model you need, download the product literature.