GP-2000 Externally Piloted Reducing Valve - Troubleshooting

When Downstream Pressure Continually Rises


Test main valve and pilot:

  • Isolate valve

  • Back adjusting bolt off

  • Remove tubing from pilot and main valve

  • Turn steam on

  • If steam leaks at top port, the pilot may be dirty
    • Replace pilot capsule K-2110
  • If steam leaks at middle port, the main valve may be dirty
    • Lap main valve and seat