Armstrong The Brain DMC2

Water Temperature Control—Recirculation Systems—Digital

DMC3

Model DMC3 features three DRV80 pre-piped in parallel and pressure tested complete with isolation valves, strainers, check valves, thermometers and pressure gauges. The Brain Model DRV80 is a fully digital recirculating valve (DRV) for “point of source” or mechanical room based installation. DRV80 is designed specifically to be the primary water temperature controller in a continuously pumped recirculating hot water system.

Operational Specifications

The enhanced accuracy possible with DRV80 digital technology, combined with its data input/output communication capability equals:

• Accurate control of blended water drawn from the systemat a point of use typically within +/-2°F at draw off pointsa minimum of 5m downstream of mixing valve duringconsistent system demand periods
• Operational water pressure of 10 -150 psig
• Minimum valve inlet to outlet temperature requirement(system recirculation temperature loss) of 2°F
• Automatic shutoff of hot water flow upon cold water inletsupply failure
• Automatic shutoff of hot water flow in the event of a powerfailure
• Maintain a consistent system “idling” temperature andcontrol Temperature Creep without the use of a manualthrottling device or balance valve.
• System shall not require a temperature activated pumpshut-off device (aquastat).
• Programmable set point range of 81-158°F (29-71°C)
• Ability to thermally disinfect at recommended temperatures
• Programmable 1st level hi/lo temp alarm display
• Programmable temperature error level for safety shutdown




Centro de descargas

Para obtener ayuda para especificar el modelo exacto que necesita, descargue la documentación del producto.

To access CAD Drawings, REGISTER or LOG IN



Biblioteca de recursos
Biblioteca de recursos
Contáctenos
Contáctenos
Représentants
Représentants
Solicitar un presupuesto
Solicitar un presupuesto
Evaluación de sistemas
Evaluación de sistemas
Calculadores
Calculadores
Ver Carro
Ver Carro