Recirculating Hot Water Systems

Parallel/Redundant Pre-Piped Tempered Water (PP-PTW)

Flo-Rite-Temp Instantaneous Steam/Water Heater for Recirculating Hot Water Systems feature four heat exchanger options offered as pre-piped parallel single temperature packaged assemblies.

Flo-Rite-Temp Pre-Piped (P-P) Parallel (P) Tempered Water (TW) Systems are fully assembled and include the following installation components:

  • Steam Trap
  • Air Vent
  • Thermometers
  • CIP Connection Port
  • Flow Control/Isolation Valves

Ideal for both new construction and retrofit installation within an existing building infrastructure. Flo-Rite-Temp Pre-Piped (P-P) Parallel (P) Tempered Water (TW) Systems are designed to fit through a standard 32" doorway (Model 8120 36" doorway).

Armstrong Flo-Rite-Temp Instantaneous Steam/Water Heater pre-piped packages are available in 58 standard configurations.

Customized Hot Water System Solutions are our specialty. Multiple orientations, configurations and options are available.

Hot Water System Solutions which include condensate recovery, circulating pumps, additional mixed water temperature controls/loops and varied other components can be application engineered specifically to meet the projects requirements.

 For submittal drawing refer to:
 Model 415PP-PTW-EMC1   Single Wall   S5480
 Model 415DWPP-PTW-EMC1   Double Wall   S5526
 Model 535PP-PTW-DMC1   Single Wall   S5481
 Model 535DWPP-PTW-DMC1   Double Wall   S5527
 Model 665PP-PTW-DMC1   Single Wall   S5482
 Model 665DWPP-PTW-DMC1   Double Wall   S5528
 Model 8120PP-PTW-DMC1   Single Wall   S5483
 Model 8120DWPP-PTW-DMC1   Double Wall   S5529

 Flo-Rite-Temp Instantaneous Steam/Water Heater
Model Entering Water Temperature Outlet Temperature
120 130 140 160 180
415PP-PTW-EMC1 40 20 18 16 12 7
50 20 20 17 13 7
60 - 20 19 14 7
535PP-PTW-DMC1 40 45 39 34 26 16
50 45 43 37 28 17
60 - 45 40 30 18
665PP-PTW-DMC1 40 80 73 63 48 32
50 80 80 68 51 33
60 - 80 75 55 35
8120PP-PTW-DMC1 40 145 145 120 95 59
50 145 145 134 102 72
60 - 145 145 115 90

Note: All flow rates in gallons per minute and using 15 PSIG steam. 

Note: If a 8120PP-PTW-DMC1 is selected for parallel operation, a second DRV 80 is recommended to increase the flow rate. 