Sizing and Selection of Air Vents


Air vents allow gases to automatically vent from liquids under pressure. The following steps will guide your selection of the appropriate vent for your steam system.

1) Estimate the amount of air to be vented in CFM at standard atmospheric pressure of 14.7 psia and 70 degrees F. (Cubic meters per minute at 1 bar and 21 degrees C)
2) Indicate the maximum operating pressure of your system.
3) Indicate the material of construction desired.
4) Indicate minimum specific gravity of the liquid.
5) Use the designated capacity to find the orifice size using the table on this page.
The table is expressed as imperial values. To view this table in SI metric units, click here.
6) Find vent or vents with the correct orifice size to handle required capacity, verifying that vent will operate at the required maximum operating pressure of the system at the required minimum specific gravity. Also, verify that selected vent is constructed of suitable materials for your application. To do this, you will need to download our Air Vents literature. pdf (438k)





Discharge of Air Through an Orifice in Standard Cubic Feet per minute
at a standard atmospheric pressure of 14.7 psia and 70°F.
Pressure psigOrifice diameter, inch
1/165/643/32#387/641/89/645/323/167/321/49/325/1611/323/87/161/29/165/83/47/81-1/16
50.651.011.451.551.982.583.274.035.817.9010.313.116.119.523.231.641.352.364.592.9126186
60.711.101.591.702.162.823.574.416.358.6411.314.317.621.325.434.545.157.170.5102138204
70.761.191.711.832.333.043.854.756.849.3112.215.419.023.027.337.248.661.576.0109149220
60.861.341.932.072.633.434.345.367.7210.513.717.421.425.930.942.054.969.485.7123168248
120.981.542.212.373.013.934.986.148.8512.015.719.924.629.735.448.262.979.698.3142193284
151.091.712.462.633.344.375.536.829.8313.417.522.127.333.039.353.569.988.4109157214316
201.251.952.813.013.824.996.327.811.215.320.025.331.237.744.961.179.8101125180245361
251.382.163.113.334.235.536.998.6312.416.922.128.034.541.849.767.788.4112138199271399
301.542.403.463.704.716.157.789.6113.818.824.631.138.446.555.375.398.4125154221301444
351.732.713.904.175.316.938.7710.815.621.227.735.143.352.462.484.9111140173250340501
401.933.014.344.645.97.719.7512.017.323.630.839.048.258.369.494.4123156193277378557
452.123.314.775.106.498.4710.713.219.126.033.942.953.064.176.3104136172212305415612
502.313.615.25.567.079.2411.714.420.828.337.046.857.769.983.1113148187231333453667
602.694.206.056.488.2310.813.616.824.232.943.054.467.281.396.8132172218269387527777
703.064.796.907.389.3912.315.519.227.637.549.062.176.692.7110150196248306441601886
803.445.377.748.2810.513.817.421.531.042.155.069.786.0104124169220279344495674994
903.815.968.589.211.715.319.323.834.346.761.077.295.31151371872443093815497471102
1004.196.549.4210.112.816.721.226.237.751.367.084.81051271512052683394196038201210
1104.567.1210.311.014.018.223.128.541.055.872.992.31141381642232923694566568931317
1255.117.9911.512.315.720.525.932.046.062.781.810412815518425132741451173710031478
1506.049.4413.614.618.524.230.637.854.474.096.712215118321729638748960487011841746
2007.8912.317.819.024.231.640.049.371.096.7126160197239284387505639789113615472281
2509.7415.221.923.529.839.049.360.987.6119156197243295351477623789974140219092814
30011.618.126.127.935.546.358.672.41041421852352903504175687419381158166822713348
40015.323.934.436.846.861.177.395.513718724430938246255074897813271527219929944414
50019.029.642.745.758.175.896.0119171232303384474574683929121415361896273137175480
60022.635.451.054.669.490.61151422042773624595666858151110145018352265326144396546
75028.244.063.467.986.311314317625434545157170485210141381180322832818405855238144
100037.458.484.190.11151501892343374585987579351131134618322393302937405385732910807

 

Example: Find a model number that will vent 52 CFM (1.47 cmm) of air (including a safety factor of 1.5 to 2.0 CFM/.04-.05 cmm) from a liquid with a specific gravity of 0.93 at 250 psi (17.24 bar). Using the table above, follow the 250 psi (17,24 bar) line across to the number 60.9(1.72). Orifice size is 5/32". Now check the vent table for the 5/32" orifice lines to locate a vent for 250 psi (17.24 bar) or higher with 0.90 gravity liquid.* The Model 3-AV is the correct vent to use in this case.

* Since specific gravity in this case falls between 0.95 and 0.90, use 0.90 gravity data.

 

 