Branch lines connect the steam main to the individual pieces of heat exchange equipment. To maintain proper operation and high efficiency, condensate must be effectively eliminated from branch piping.
The following formulas are expressed as imperial values.
To view this page in SI metric units, click here.

Traps are best suited to branch line applications if they:
The inverted bucket trap meets all of these requirements best. In non-freezing environments below 30 psig (2 bar), the float and thermostatic trap is an acceptable alternative. An alternate choice in a freezing environment is the thermostatic trap or controlled disc trap.


MATH |
|
To determine trap capacity necessary for installation:
|
Safety Factor |
|
The safety factor recommendation for branch lines is 3:1. |
Load CalculationCalculate using a formula |
||||||||||||||||
|
C =
|
Condensate in lbs/hr-foot |
|
A =
|
External area of pipe in square feet (Table 17-1, Col. 2 below) |
|
U =
|
Btu/sq ft/degree temperature difference/hr from Chart 17-1 below |
|
t1 =
|
Steam temperature in °F |
|
t2 =
|
Air temperature in °F |
|
E =
|
1 minus efficiency of insulation (Example: 75 percent efficient insulation: 1-.75 = .25 or E = .25) |
|
H =
|
Latent heat of steam (See Steam Table) |
| * Handbook N-101 (1.3 MB) |