Absorption Tanks - Trap


Traps best serve this application when they:

  • continuously drain the steam space
  • conserve energy over a long service life
  • vent air at very low pressure (1/4 psig/.02 bar)

These requirements combine to make the float and thermostatic (F&T) trap the best selection for this application. A suitable alternative would be an inverted bucket (IB) trap with an external thermostatic air vent.

  Characteristic
Inverted
Bucket
F&T
Disc  Thermostatic 
Differential
Controller
A Method of Operation  Intermittent  Continuous  Intermittent  Intermittent  Continuous
B Energy Conservation (Time in Service)  Excellent  Good  Poor  Fair Excellent
C Resists Wear  Excellent  Good  Poor  Fair Excellent
D Resists Corrosion  Excellent  Good  Excellent  Good Excellent
E Resists Hydraulic Shock  Excellent  Poor  Excellent  Poor Excellent
F Vents Air and CO2 at Steam Temperature  Yes  No  No  No Yes
G Vents Air at Very Low Pressure
(1/4 psig)(.02 bar)
 Poor  Excellent  NR  Good Excellent
H Handles Start-up Air Loads  Fair  Excellent  Poor  Excellent Excellent
I Operates Against Back Pressure  Excellent  Excellent  Poor  Excellent  Excellent
J Resists Damage from Freezing  Good  Poor  Good  Good Good
K Can Purge System  Excellent  Fair  Excellent  Good Excellent
L Performs on Very Light Loads  Excellent  Excellent  Poor  Excellent Excellent
M Responds to Slugs of Condensate  Immediate  Immediate  Delayed  Delayed  Immediate
N Handles Dirt  Excellent  Poor  Poor Fair Excellent
O Comparative Physical Size  Large  Large Small  Small Large
P Handles "Flash Steam"  Fair  Poor  Poor  Poor  Excellent
Q Mechanical Failure (Open -- Closed)  Open  Closed  Open Open, Closed Open
                     
First Choice       Alternative       Overriding condition    